Home » Products » Water Loop Heat Pump » Packaged Units

Packaged Units

Model Horiz- ontal VWLN 025H VWLN 028H VWLN 032H VWLN 044H VWLN 050H VWLN 062H VWLN 078H VWLN 088H VWLN 095H VWLN 110H VWLN 130H VWLN 170H VWLN 250H
Vertical VWLN 025V VWLN 028V VWLN 032V VWLN 044V VWLN 050V VWLN 062V VWLN 078V VWLN 088V VWLN 095V VWLN 110V VWLN 130V VWLN 170V VWLN 250V
Nominal Cooling Capacity kW 2.42 2.81 3.14 4.35 5.01 6.16 7.79 8.8 9.51 10.7 13.19 16.62 24.33
Nominal Heating Capacity kW 2.66 3.09 3.45 4.79 5.51 6.78 8.57 9.68 10.46 11.77 14.51 18.28 26.76
Nominal Air Flow m3/h 450 500 560 780 900 1100 1400 1600 1700 1930 2400 3000 4400
CFM 265 294 329 459 529 647 824 941 1000 1135 1412 1765 2588
Static Pressure Pa 10 10 10 30 30 30 30 30 30 30 50 80 100
Power Supply V/pH/Hz 220V/1pH/50HZ 380V/3pH/50HZ
Power Colling Input W 620 700 800 1100 1240 1530 1940 2200 2000 2300 2840 3520 4730
Power Heating Input W 645 730 830 1150 1300 1600 2020 2080 2290 2390 2980 3690 4930
Rated Cooling Current A 3.1 3.5 4 5.5 6.2 7.65 9.7 10 11 11.5 5.7 7 9.1
Rated Heating Current A 3.2 3.7 4.2 5.8 6.5 8.0 10.1 10.4 11.5 12.0 5.9 7.2 9.4
Refrigerant Type R22
Compressor Rotator Scroll
Water Flow m3/h 0.52 0.60 0.68 0.94 1.08 1.47 1.67 1.89 1.98 2.43 2.76 3.46 5.00
Water Pressure Drop kPa 12 23 45 21 27 40 42 40 40 40 40 43 62
Inlet/Outlet Pipe   Rc1/2 Rc1/2 Rc1/2 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc3/4 Rc1
Dimensions Horizontal Length (mm) 1033 1033 1033 1033 1033 1033 1033 1233 1233 1233 1233 1333 1800
Width (mm) 535 535 535 535 535 535 535 715 715 715 715 790 1000
Height (mm) 375 375 375 420 420 420 420 500 500 500 500 500 650
Vertical Length (mm) 550 550 550 550 550 550 550 550 630 630 630 710 710
Width (mm) 550 550 550 550 550 550 550 550 630 630 630 710 1060
Height (mm) 790 790 790 790 790 790 940 940 1090 1090 1190 1190 1190
Weight Horizontal kg 60 62 64 72 72 76 80 90 100 110 120 150 190
Vertical kg 80 85 90 95 100 110 120 125 133 150 160 175 220
Condenser Pipe in R1/2 R1/2 R1/2 R1/2 R1/2 R1/2 R1/2 R1/2 R1/2 R1/2 R1/2 R1/2 R3/4

Note
1. Noise data is measured in semi-anechoic rooms according to the relative national system requirements.
2. Nominal cooling capacity is measured in condition: Indoor D.B.: t(d)=27℃ W.B.: t (w)= 19℃; water inlet temperature: t=30℃; water outlet temperature: t= 35℃. Nominal heating capacity is measured in condition: Indoor D.B.: t(d)=20℃ W.B.: t(w)=15℃; water inlet temperature: t=20℃.
3. Standard data will be varied with products improving, please take the data marked on nameplates of units as standard.